Model   CVF 200   CVF 300   CVF 400   CVF 600   CVF 800
Nominal air volume m3/s 2   3   4   6   8
Maximum Dehumidification
effect kg/hr
1) 84   126   168   251   336
  2) 40   61   81   122   162
  3) 90   135   180   270   360
                     
Supply fan motor kW 4.1   4.1   5.5   11   15
Sound power level dBA 84   89   93   97   98
External resistance Pa 200   200   200   200   200
Specific fan power W/(l/s) 1.5   1.4   1.1   1.3   1.3
Return fan motor kW 4.1   4.1   5.5   11   15
Sound power level dBA 81   89   93   95   96
External resistance Pa 200   200   200   200   200
Specific fan power W/(l/s) 1.4   1.3   1.1   1.1   1.1
 
Recuperator nominal Eff % 56   51   55   55   53
LPHW coil duty kW 57   85   113   172   250
LPHW flow rate l/s 1.25   1.9   2.5   3.78   5.4
LPHW pressure drop kPa 24   25   25   26   26
Max fabric loss capability kW 32   48   64   75   100
Maximum power consumption kW 6   8.2   9   18   24
Nominal power consumption kW 3.1   4   4.5   9   12
Full load current Amps 13   13.6   23   32   44
                     
. 
Length mm 2400   2600   3000   4000   5000
Width mm 1600   1600   1600   2400   2600
Height mm 1800   1900   2300   2800   2800
Weight kg 900   1000   1500   2500   2800
                     
1) Winter Fresh air at 0°C 100% RH Pool hall condition 30°C 50% RH
2) Summer Fresh air at 28°C 47% RH Pool hall condition 30°C 60% RH
3) Average Fresh air at 8°C 80% RH Pool hall condition 30°C 58% RH

Larger units are available, contact out office for details