| Model | VFHE 50 | VFHE 100 | VFHE 150 | VFHE 200 | |
|
Nominal air volume |
m3/s |
0.5 |
1.0 |
1.5 |
2.0 |
|
Maximum Dehumidification |
1) |
27 |
54 |
81 |
108 |
|
2) |
10 |
20 |
30 |
40 |
|
|
3) |
24 |
47 |
71 |
94 |
|
|
Supply fan motor |
kW |
1.15 |
1.8 |
2.5 |
2.5 |
|
Sound power level |
dBA |
78 |
89 |
93 |
93 |
|
External resistance |
Pa |
200 |
200 |
200 |
200 |
|
Specific fan power |
W/(l/s) |
1.7 |
1.475 |
1.4 |
1.2 |
|
Return fan motor |
kW |
0.69 |
1.15 |
1.8 |
2.5 |
|
Sound power level |
dBA |
74 |
89 |
93 |
93 |
|
External resistance |
Pa |
200 |
200 |
200 |
200 |
|
Specific fan power |
W/(l/s) |
1.16 |
1.1 |
1.13 |
0.8 |
|
Recuperator nominal Eff |
% |
67 |
72 |
72 |
66 |
|
LT LPHW coil duty |
kW |
15 |
31 |
46 |
62 |
|
LT LPHW flow rate |
l/s |
0.19 |
0.374 |
0.561 |
0.747 |
|
LT LPHW pressure drop |
kPa |
12 |
15 |
20 |
17 |
|
Max fabric loss capability |
kW |
11 |
21.5 |
30.8 |
42.5 |
|
Maximum power consumption |
kW |
1.9 |
3 |
4.3 |
5 |
|
Nominal power consumption |
kW |
0.23 |
0.38 |
0.54 |
0.63 |
|
Full load current (single phase) |
Amps |
7 |
12 |
16 |
18 |
|
Full load current (three phase) |
Amps |
3.8 |
6 |
8 |
9 |
|
Length |
mm |
850 |
1000 |
1100 |
1400 |
|
Width |
mm |
750 |
850 |
1150 |
1500 |
|
Height |
mm |
1800 |
1950 |
2200 |
2275 |
|
Weight |
kg |
370 |
450 |
550 |
750 |
| Duct Connection sizes (HxL): | |||||
|
Fresh Air Inlet |
mm |
410 x 650 |
510 x 650 |
510 x 900 |
650 x 1200 |
|
Supply Air Outlet |
mm |
300 x 550 |
300 x 650 |
300 x 900 |
400 x 1200 |
|
Return Air Inlet |
mm |
500 x 500 |
600 x 600 |
900 x 900 |
900 x 900 |
|
Exhaust Air Outlet |
mm |
200 x 550 |
220 x 650 |
300 x 900 |
300 x 1200 |
|
1) Winter Fresh air at 0°C 100% RH Pool hall condition 30°C 60% RH |
|||||