Model   VFHE 50 VFHE 100 VFHE 150 VFHE 200

Nominal air volume

m3/s

0.5

1.0

1.5

2.0

Maximum Dehumidification
effect kg/hr

1)

27

54

81

108

2)

10

20

30

40

3)

24

47

71

94

 

Supply fan motor

kW

1.15

1.8

2.5

2.5

Sound power level

dBA

78

89

93

93

External resistance

Pa

200

200

200

200

Specific fan power

W/(l/s)

1.7

1.475

1.4

1.2

 

Return fan motor

kW

0.69

1.15

1.8

2.5

Sound power level

dBA

74

89

93

93

External resistance

Pa

200

200

200

200

Specific fan power

W/(l/s)

1.16

1.1

1.13

0.8

 

Recuperator nominal Eff

%

67

72

72

66

LT LPHW coil duty

kW

15

31

46

62

LT LPHW  flow rate

l/s

0.19

0.374

0.561

0.747

LT LPHW  pressure drop

kPa

12

15

20

17

Max fabric loss capability

kW

11

21.5

30.8

42.5

Maximum power consumption

kW

1.9

3

4.3

5

Nominal power consumption

kW

0.23

0.38

0.54

0.63

Full load current (single phase)

Amps

7

12

16

18

Full load current (three phase)

Amps

3.8

6

8

9

 

Length

mm

850

1000

1100

1400

Width

mm

750

850

1150

1500

Height

mm

1800

1950

2200

2275

Weight

kg

370

450

550

750

Duct Connection sizes (HxL):

Fresh Air Inlet

mm

410 x 650

510 x 650

510 x 900

650 x 1200

Supply Air Outlet

mm

300 x 550

300 x 650

300 x 900

400 x 1200

Return Air Inlet

mm

500 x 500

600 x 600

900 x 900

900 x 900

Exhaust Air Outlet

mm

200 x 550

220 x 650

300 x 900

300 x 1200

1) Winter Fresh air at 0°C 100% RH Pool hall condition 30°C 60% RH
2) Summer Fresh air at 28°C 47% RH Pool hall condition 30°C 60% RH
3) Average Fresh air at 8°C 80% RH Pool hall condition 30°C 60% RH